Signals
Table 118:
SR Input signals
Name
Type
Default
Description
S
BOOLEAN
0=False
Set Q output when set
R
BOOLEAN
0=False
Resets Q output when
set
Table 119:
SR Output signals
Name
Type
Description
Q
BOOLEAN
Q status
NOTQ
BOOLEAN
NOTQ status
3.16.1.13
RS function block
Function block
GUID-3876F400-A7D1-45DA-B20F-DFA5AE863073 V1 EN
Figure 77:
Function block
Functionality
The RS flip-flop output
Q
can be set or reset from the
S
or
R
inputs.
R
input has a higher
priority over the
S
input. Output
NOTQ
is the negation of output
Q
.
The statuses of outputs
Q
and
NOTQ
are not retained in the nonvolatile
memory.
Table 120:
Truth table for RS flip-flop
S
R
Q
0
0
0
1)
0
1
0
1
0
1
1
1
0
1) Keep state/no change
Section 3
1MRS758755 A
Basic functions
132
REC615 and RER615
Technical Manual