Signals
Table 115:
SWITCHI32 input signals
Name
Type
Default
Description
CTL_SW
BOOLEAN
1
Control Switch
IN1
INT32
0
Input signal 1
IN2
INT32
0
Input signal 2
Table 116:
SWITCHI32 output signals
Name
Type
Description
OUT
INT32
Output signal
3.16.1.12
SR function block
Function block
GUID-0B62CAED-F8A4-4738-B546-677DA362FE24 V2 EN
Figure 76:
Function block
Functionality
The SR flip-flop output
Q
can be set or reset from the
S
or
R
inputs.
S
input has a higher
priority over the
R
input. Output
NOTQ
is the negation of output
Q
.
The statuses of outputs
Q
and
NOTQ
are not retained in the nonvolatile
memory.
Table 117:
Truth table for SR flip-flop
S
R
Q
0
0
0
1)
0
1
0
1
0
1
1
1
1
1) Keep state/no change
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
131
Technical Manual