Settings
The function does not have any parameters available in LHMI or PCM600.
3.16.1.3
XOR function block
Function block
GUID-9C247C8A-03A5-4F08-8329-F08BE7125B9A V1 EN
Figure 67:
Function block
Functionality
The exclusive OR function XOR is used to generate combinatory expressions with
Boolean variables.
The output signal is TRUE if the input signals are different and FALSE if they are
equal.
Signals
Table 93:
XOR Input signals
Name
Type
Default
Description
B1
BOOLEAN
0
Input signal 1
B2
BOOLEAN
0
Input signal 2
Table 94:
XOR Output signal
Name
Type
Description
O
BOOLEAN
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.16.1.4
NOT function block
Function block
GUID-0D0FC187-4224-433C-9664-908168EE3626 V1 EN
Figure 68:
Function block
Section 3
1MRS758755 A
Basic functions
124
REC615 and RER615
Technical Manual