Table 75:
Conversion from integer to Boolean
IN
RAISE
LOWER
0
FALSE
FALSE
1
FALSE
TRUE
2
TRUE
FALSE
x
FALSE
FALSE
3.15.8.3
Signals
Table 76:
T_TCMD_BIN input signals
Name
Type
Default
Description
IN
INT32
0
Input signal
Table 77:
T_TCMD_BIN output signals
Name
Type
Description
RAISE
BOOLEAN
Raise command
LOWER
BOOLEAN
Lower command
3.15.9
T_BIN_TCMD function block
3.15.9.1
Function block
GUID-54A013A3-E253-4A06-B033-01C7E11EC997 V1 EN
Figure 64:
Function block
3.15.9.2
Functionality
The T_BIN_TCMD function is used to convert Boolean input signals to 32 bit integer
output signals.
Table 78:
Conversion from Boolean to integer
RAISE
LOWER
OUT
FALSE
FALSE
0
FALSE
TRUE
1
TRUE
FALSE
2
Section 3
1MRS758755 A
Basic functions
118
REC615 and RER615
Technical Manual