9.6.2
Setting guidelines
SEMOD55228-5 v2
There are no setting parameters for the Signal matrix for binary outputs SMBO available to the
user in Parameter Setting tool. However, the user must give a name to SMBO instance and
SMBO outputs, directly in the Application Configuration tool. These names will define SMBO
function in the Signal Matrix tool.
9.7
Signal matrix for mA inputs SMMI
SEMOD55233-1 v2
9.7.1
Application
SEMOD55237-5 v2
The Signal matrix for mA inputs function SMMI is used within the Application Configuration
tool in direct relation with the Signal Matrix tool. SMMI represents the way milliamp (mA)
inputs are brought in for one IED configuration.
9.7.2
Setting guidelines
SEMOD55247-5 v2
There are no setting parameters for the Signal matrix for mA inputs SMMI available to the user
in the Parameter Setting tool. However, the user must give a name to SMMI instance and SMMI
inputs, directly in the Application Configuration tool.
9.8
Test mode functionality TESTMODE
IP1647-1 v3
9.8.1
Application
M11407-3 v9
The protection and control IEDs may have a complex configuration with many included
functions. To make the testing procedure easier, the IEDs include the feature that allows
individual blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enables the
user to follow the operation of several related functions to check correct functionality and to
check parts of the configuration, and to check parts.
9.8.1.1
IEC 61850 protocol test mode
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v5
The function block TESTMODE has implemented the extended testing mode capabilities for
IEC 61850 Ed2 systems. Operator commands sent to the function block TESTMODE determine
the behavior of the functions. The command can be given remotely from an IEC 61850 client or
from the LHMI under the Main menu/Test/Function test modes/Communication/Station
Communication/IEC61850 LD0 LLN0/LD0LLN0:1. The possible values of the function block
TESTMODE are described in
Communication protocol manual, IEC 61850 Edition 1 and Edition
2.
There is no setting in PCM600 via PST for the TESTMODE function block.
1MRK 511 445-UEN B
Section 9
Basic IED functions
Switchgear control unit SAM600-IO
71
Application manual