Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-tested
settings in advance for different protection functions. Six different groups of setting
parameters are available in the IED. Any of them can be activated through the different
programmable binary inputs by means of external or internal control signals.
A function block, SETGRPS, defines how many setting groups are used. Setting is done with
parameter
MAXSETGR and shall be set to the required value for each IED. Only the number of
setting groups set will be available in the Parameter Setting tool for activation with the
ActiveGroup function block.
9.4.2
Setting guidelines
M15259-3 v4
The setting
ActiveSetGrp, is used to select which parameter group to be active. The active
group can also be selected with configured input to the function block SETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active group has
changed, is set with the parameter
t.
The parameter
MAXSETGR defines the maximum number of setting groups in use to switch
between. Only the selected number of setting groups will be available in the Parameter Setting
tool (PST) for activation with the ActiveGroup function block.
9.5
Signal matrix for binary inputs SMBI
SEMOD55793-1 v2
9.5.1
Application
M15310-3 v2
The Signal matrix for binary inputs function SMBI is used within the Application Configuration
tool in direct relation with the Signal Matrix tool. SMBI represents the way binary inputs are
brought in for one IED configuration.
9.5.2
Setting guidelines
M15312-3 v3
There are no setting parameters for the Signal matrix for binary inputs SMBI available to the
user in Parameter Setting tool. However, the user shall give a name to SMBI instance and the
SMBI inputs, directly in the Application Configuration tool. These names will define SMBI
function in the Signal Matrix tool. The user defined name for the input or output signal will also
appear on the respective output or input signal.
9.6
Signal matrix for binary outputs SMBO
SEMOD55215-1 v2
9.6.1
Application
SEMOD55213-5 v4
The Signal matrix for binary outputs function SMBO is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMBO represents the way
binary outputs are sent from one IED configuration.
Section 9
1MRK 511 445-UEN B
Basic IED functions
70
Switchgear control unit SAM600-IO
Application manual