designed for receiving up to 16 booleans input locally. If the BLOCK input is activated, it will
freeze the output at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block BTIGAPC.
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the BTIGAPC function block.
4.10
Integer to Boolean 16 conversion IB16
SEMOD158367-1 v2
4.10.1
Identification
SEMOD167941-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion
IB16
-
-
4.10.2
Application
SEMOD158499-5 v4
Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
binary (logical) signals. It can be used – for example, to connect integer output signals from
one function to binary (logical) inputs to another function. IB16 function does not have a
logical node mapping.