At control with enhanced security there is an additional supervision of the status value by the
control object, which means that each command sequence must be terminated by a
termination command.
The parameter
PosDependent gives permission to operate depending on the position
indication, that is, at
Always permitted it is always permitted to operate independent of the
value of the position. At
Not perm at 00/11 it is not permitted to operate if the position is in
bad or intermediate state.
tSelect is the maximum allowed time between the select and the execute command signal,
that is, the time the operator has to perform the command execution after the selection of the
object to operate. When the time has expired, the selected output signal is set to false and a
cause-code is given.
The time parameter
tResResponse is the allowed time from reservation request to the
feedback reservation granted from all bays involved in the reservation function. When the time
has expired, the control function is reset, and a cause-code is given.
tSynchrocheck is the allowed time for the synchrocheck function to fulfill the close conditions.
When the time has expired, the function tries to start the synchronizing function. If
tSynchrocheck is set to 0, no synchrocheck is done, before starting the synchronizing function.
The timer
tSynchronizing supervises that the signal synchronizing in progress is obtained in
SCSWI after start of the synchronizing function. The start signal for the synchronizing is set if
the synchrocheck conditions are not fulfilled. When the time has expired, the control function
is reset, and a cause-code is given. If no synchronizing function is included, the time is set to
0,
which means no start of the synchronizing function is done, and when
tSynchrocheck has
expired, the control function is reset and a cause-code is given.
tExecutionFB is the maximum time between the execute command signal and the command
termination. When the time has expired, the control function is reset and a cause-code is
given.
tPoleDiscord is the allowed time to have discrepancy between the poles at control of three
one-phase breakers. At discrepancy an output signal is activated to be used for trip or alarm,
and during a command, the control function is reset, and a cause-code is given.
SuppressMidPos when On suppresses the mid-position during the time tIntermediate of the
connected switches.
The parameter
InterlockCheck decides if interlock check should be done at both select and
operate, Sel & Op phase, or only at operate, Op phase.
3.2
Logic rotating switch for function selection SLGAPC
SEMOD114936-1 v5
3.2.1
Identification
SEMOD167845-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic rotating switch for function
selection and LHMI presentation
SLGAPC
-
-
Section 3
1MRK 511 445-UEN B
Control
22
Switchgear control unit SAM600-IO
Application manual
© Copyright 2017 ABB. All rights reserved