Directional mode Zx
Pol. = polarization method affects (mho) zone shape
Pol. Pol.
X
R
X
R
X
R
Non-directional
Forward
Reverse
Figure 555: Bullet combi tripping characteristic. Pol. in the figure means the shape
of the characteristic is affected by the selected polarization method, Pol quantity
zone = "Cross pol", "Pos. seq. volt.", "Self pol"
4.7.1.6
Recorded data
The required information for later fault analysis is recorded when the recording
function of DSTPDIS is triggered by activating
TRIGG_REC
input or writing to the
corresponding DO “LD0.GFCPDIS1.RcdTrg.Oper.ctlVal”. During external triggering
(input signal
TRIGG_REC
), the recorded data of all zones and the phase selection
function are recorded.
A total of three sets of recorded data are saved in data banks Fault 1, 2 and 3. Data
bank Fault 1 holds the most recent recorded data and the older data is moved into
the following banks (1->2 and 2->3) when triggering occurs. When all three banks
have data and a new triggering occurs, the latest data is placed into bank 1 and the
data in bank 3 is overwritten by the data from bank 2.
Table 923: Recorded data for the phase selection function
Parameter name
Description
Time
Recorded data time stamp
Release PE-loop
Release signals for PE loops, GFC
Release PP-loop
Release signals for PP/3P loops, GFC
Earth fault detected
Indication of a single-phase earth fault, GFC
Cross country fault
Indication of a cross-country fault (high imp.
earthed), GFC
Earth fault direction
Earth-fault direction (low imp. earthed), GFC
Operate of all zones
Operate signals of all zones (this is zone infor-
mation but it is taken here because it represents
all zone information combined)
Protection functions
1MRS759142 F
980
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......