Figure 541: The fault loop impedance model for three-phase impedance measuring
element
R
1
Positive-sequence resistance from measuring point to fault location
X
1
Positive-sequence reactance from measuring point to fault location.
R
F
Physical fault resistance per phase, for example, arc resistance.
The three-phase impedance measuring element measures the physical
fault resistance per phase. The resistive reach setting is common for
three-phase and phase-to-phase impedance measuring elements.
The time delay of operation is defined with the
PP operate delay Znx (x = 1...
5) setting. The timer can be disabled with the setting
PP Op delay Mod Znx =
"False". This blocks the
OPERATE_Zx
(x = 1... 5) output of the three-phase measuring
elements.
Entering the line reach
The line reach is entered in primary ohms. The impedance format is selected
with
Impedance mode Zn = "Rectangular" for the vectors R, X and "Polar" for the
magnitude and angle.
Impedance mode Zn = Rectangular
In case of phase-to-phase or three-phase impedance measuring elements, the line
reach is defined with:
• Resistive reach:
R1 zone x (x = 1...5)
• Reactive reach:
X1 zone x (x = 1...5)
In case of non-directional characteristics, the reactive reach in reverse direction is
defined with the
X1 reverse zone x (x = 1...5) setting. The characteristic line angle,
denoted as α, is the same for both forward and reverse direction.
1MRS759142 F
Protection functions
REX640
Technical Manual
969
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......