3.2.13
Modbus protocol MBSLPRT
3.2.13.1
Function block
MBSLPRT1
STATUS
Figure 19: Function block
3.2.13.2
Functionality
The function block represents a Modbus server protocol instance in the protection
relay. Function block settings include communication interface assignment for the
instance, that is, Ethernet/TCP or serial.
A Modbus server protocol instance is activated if the function block instance is
added to the application configuration. The setting
Operation should be "On" and
setting
Port should have the communication interface assignment.
The
STATUS
output of the function block is active if Modbus client requests have
been received on the communication interface within 15 seconds.
By default no Modbus data is mapped to the protocol interface. Protocol data
has to be created using Communication Management in PCM600. There are two
mapping sets, “Mapping 1” and “Mapping 2”, and either can be used. Setting
parameter
Mapping selection points to the mapping set used. Several Modbus
protocol instances can point to the same mapping set.
For more information on the Modbus server protocol, see the Modbus
communication protocol manual.
3.2.14
DNP3 protocol DNPLPRT
3.2.14.1
Function block
DNPLPRT1
STATUS
Figure 20: Function block
3.2.14.2
Functionality
The function block represents one DNP3 server protocol instance in the protection
relay. Function block settings include communication interface assignment for the
instance, that is, Ethernet/TCP(+UDP) or serial.
Over Ethernet/TCP, the protocol optionally supports secure authentication with
symmetric keys. The implementation follows the IEC 62351-5 security standard
specification as well as the descriptions in DNP3 standard part 7, IP-networking
chapter "Secure authentication".
1MRS759142 F
Basic functions
REX640
Technical Manual
95
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......