
The recommended and the default value for
Phase supervision is “Pos
sequence”.
If the magnitude of the voltage level of any of the monitored voltage signal, defined
by the
Phase supervision setting, drops below Under Volt Blk value or exceeds Over
Volt Blk value, the calculation of vector shift is disabled and the
INT_BLKD
output is
activated.
The function is blocked and
LOWAMPL_BLKD
is activated, if the measured frequency
deviates ±5% from the nominal value.
The magnitude of calculated vector shift for three phase-to-earth or phase-
to-phase voltages, USHIFT_A_AB, USHIFT_B_BC and USHIFT_C_CA or positive
sequence voltage U1SHIFT, which resulted in the activation of last
OPERATE
output,
are available in the Monitored data view.
The activation of
BLOCK
input deactivates the
INT_BLKD
output.
Figure 510: Vector shift during Loss of Mains
Pulse timer
Once the Pulse timer is activated, it activates the
OPERATE
output. The pulse length
of
OPERATE
is fixed to 100 ms.
The activation of the
BLOCK
input deactivates the
OPERATE
binary output and resets
the timer.
4.5.9.6
Application
Use of distributed generation ( DG) units is increasing due to liberalized markets
(deregulation) and the global trend to use more renewable sources of energy. They
generate power in the range of 10 kW...10 MW and most of them are interconnected
to the distribution network. They can supply power into the network as well as to
the local loads. It is not common to connect generators directly to the distribution
networks and thus the distributed generation can cause some challenges for the
protection of distribution networks. From the protection point of view, one of the
most challenging issue is islanding.
Islanding is defined as a condition in which a distributed generation unit continues
to supply power to a certain part of the distribution network when power from the
Protection functions
1MRS759142 F
910
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......