3.2.7.1
Function block
Figure 15: Function block
3.2.7.2
Functionality
The function block represents the IEC61850 GOOSE communication monitoring and
diagnostics in the relay. Function block includes the GOOSE diagnostic counters
that can be accessed via HMI, and
ALARM
output.
ALARM
output indicates if overall GOOSE communication status is good or not.
If
ALARM
output status is “False”, all GOOSE inputs are receiving data within the
timeout limits. If the output is “True”, there is an issue (e.g. timeout or decoding),
with one or more of GOOSE inputs in the relay.
For more information on the GOOSE configuration and monitoring refer to the
IEC61850 engineering manual.
3.2.8
Serial port supervision SERLCCH
3.2.8.1
Function block
SERLCCH1
CH1LIV
LNK1LIV
Figure 16: Function block
3.2.8.2
Functionality
The serial port supervision function SERLCCH represents one serial communication
port driver. Depending on the hardware configuration, the protection relay can be
equipped with two UART-based serial communication ports. The communication
ports can be both galvanic (RS-485) or one port could be fiber-optic. The protection
relay uses the ports for serial communication protocol links.
Serial communication drivers are identified in the device configuration as COM1
and COM2, which correspond to function blocks SERLCCH1 and SERLCCH2,
respectively. Each COM port driver has its own setting parameters on the HMI under
Configuration > Communication > COMn (n=1,2).
Output
LNKxLIV
is active (TRUE) whenever characters are received on the serial
interface. Output
CHxLIV
is active (TRUE) while complete link frames are received.
Both outputs go to FALSE state after 15 seconds of inactivity on the port.
Basic functions
1MRS759142 F
90
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......