Figure 499: Example of an inverse time counter operation if START occurs when
BLK_RESTART is inactive while COOL_ACTIVE is active.
4.5.7.7
Application
If the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its designed limits, the leakage flux increases. This
results in a heavy hysteresis and eddy current losses in the non-laminated parts.
These losses can cause excessive heating and severe damage to the insulation and
adjacent parts in a relatively short time.
Overvoltage, underfrequency or a combination of the two, results in an excessive
flux density level. Since the flux density is directly proportional to the voltage and
inversely proportional to the frequency, the overexcitation protection calculates the
relative V/Hz ratio instead of measuring the flux density directly. The nominal level
(nominal voltage at nominal frequency) is usually considered as the 100 percent
level, which can be exceeded slightly based on the design.
The greatest risk for overexcitation exists in a thermal power station when the
generator-transformer unit is disconnected from the rest of the network or in the
network islands where high voltages or low frequencies can occur.
Overexcitation can occur during the start-up and shutdown of the generator if
the field current is not properly adjusted. The loss-of-load or load shedding can
also result in overexcitation if the voltage control and frequency governor do not
function properly. The low frequency in a system isolated from the main network
can result in overexcitation if the voltage-regulating system maintains a normal
voltage.
Overexcitation protection for the transformer is generally provided by the generator
overexcitation protection, which uses the VTs connected to the generator terminals.
The curves that define the generator and transformer V/Hz limits must be
coordinated properly to protect both equipment.
If the generator can be operated with a leading power factor, the high-side voltage
of the transformer can have a higher pu V/Hz than the generator V/Hz. This needs
1MRS759142 F
Protection functions
REX640
Technical Manual
893
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......