4.4.5.10
MNSPTOC Monitored data
Table 775: MNSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
T_ENARESTART
INT32
0...10000
s
Estimated time to reset
of block restart
MNSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.5.11
Technical data
Table 776: MNSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±1.5% of the set value or ±0.002 × I
n
Start time
1, 2
I
Fault
= 2.0 × set
Start value
Minimum
Typical
Maximum
23
25 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.4.5.12
Technical revision history
Table 777: MNSPTOC Technical revision history
Product connectivity
level
Technical revision
Change
PCL2
E
Added new input
ST_EMERG_ENA
which al-
lows motor energization in an emergency
case
4.5
Voltage protection
1
Negative-sequence current before = 0.0, f
n
= 50 Hz, results based on statistical distribution of
1000 measurements.
2
Includes the delay of the signal output contact.
3
Start value multiples in range of 1.10...5.00.
Protection functions
1MRS759142 F
850
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......