measurement conductors have a resistance of 0.113 Ω, the actual burden of
the current transformer is S
a
= (5A)² × (0.113 + 0.020) Ω = 3.33 VA. Thus, the
accuracy limit factor F
a
corresponding to the actual burden is about 46.
The CT burden can grow considerably at the rated current 5A. The actual burden of
the current transformer decreases at the rated current of 1 A while the repeatability
simultaneously improves.
At faults occurring in the protected area, the fault currents can be very
high compared to the rated currents of the current transformers. Due to
the instantaneous stage of the differential function block, it is sufficient that
the current transformers are capable of repeating the current required for an
instantaneous tripping during the first cycle.
Thus the current transformers usually are able to reproduce the asymmetric fault
current without saturating within the next 10 ms after the occurrence of the fault to
secure the operating times of the protection relay comply with the retardation time.
The accuracy limit factors corresponding to the actual burden of the phase current
transformer to be used in differential protection must fulfill the requirement:
F
K
Ik
T
e
a
r
dc
T
m
Tdc
>
×
×
×
×
−
+
−
max
(
(
)
)
ω
1
1
(Equation 210)
Ik
max
The maximum through-going fault current (in I
R
) at which the protection is not
allowed to operate
T
dc
The primary DC time constant related to Ik
max
ω
The angular frequency, that is, 2 x π x f
n
T
m
The time to saturate, that is, the duration of the saturation-free transforma-
tion
K
r
The remanence factor 1/(1-r), where r is the maximum remanence flux in pu
from the saturation flux
The parameter r is the maximum remanence flux density in the CT core in pu from
the saturation flux density. The value of the parameter r depends on the magnetic
material used and also on the construction of the CT. For instance, if the value r
= 0.4, the remanence flux density can be 40 percent of the saturation flux density.
The manufacturer of the CT has to be contacted when an accurate value for the
parameter r is needed. The value r = 0.4 is recommended to be used when an
accurate value is not available.
The required minimum time-to-saturate T
m
in MPDIF is half-fundamental cycle
period (10 ms when f
n
= 50 Hz).
Two typical cases are considered for the determination of the sufficient actual
accuracy limit factor F
a
:
Protection functions
1MRS759142 F
796
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......