Parameter
Values (Range)
Unit
Step
Default
Description
1=True
Slot specific hyste-
resis
0=False
1=True
0=False
Use slot specific bi-
nary input voltage
hysteresis
Input threshold
voltage
16...176
Vdc
2
16
Global binary input
threshold for all
slots
Input threshold
hysteresis
10...50
%
2
10
Global binary input
hysteresis for all
slots
Input osc. level
2...50
events/s
1
30
Binary input oscil-
lation suppression
threshold
Input osc. hyst
2...50
events/s
1
10
Binary input oscil-
lation suppression
hysteresis
3.2
Communication
The protection relay supports a range of communication protocols including IEC
61850, IEC 61850-9-2 LE, IEC 60870-5-103, IEC 60870-5-104, Modbus
®
and DNP3.
Profibus DPV1 communication protocol is supported by using the protocol converter
SPA-ZC 302. Operational information and controls are available through these
protocols. However, some communication functionality, for example, horizontal
communication between the protection relays, is only enabled by the IEC 61850
communication protocol.
One full IEC 61850-9-2 LE stream containing both voltages and currents can be
sent. Receiving of up to four SMV streams is supported with a total of maximum
16 channels. The channels are freely configurable with the possibility to engineer
SMV stream redundancy using the voltage and current switch functions with
either another SMV stream or local measurements. The SMV stream quality along
with other Application Configuration logic can be used for switching between
measurement sources.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault
records can be accessed using the IEC 61850 protocol. Disturbance recordings
are available to any Ethernet-based application in the IEC 60255-24 standard
COMTRADE file format. The protection relay can send and receive binary signals
from other devices (so-called horizontal communication) using the IEC 61850-8-1
GOOSE profile, where the highest performance class with a total transmission time
of 3 ms is supported. Furthermore, the protection relay supports sending and
receiving of analog values using GOOSE messaging. The protection relay meets
the GOOSE performance requirements for tripping applications in distribution
substations, as defined by the IEC 61850 standard.
The protection relay can support five simultaneous clients. If PCM600 reserves one
client connection, only four client connections are left, for example, for IEC 61850
and Modbus.
All communication connectors are placed on integrated optional communication
modules. The protection relay can be connected to Ethernet-based communication
systems via the RJ-45 connector (100Base-TX) or the fiber-optic LC connector
(100Base-FX).
1MRS759142 F
Basic functions
REX640
Technical Manual
79
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......