(Equation 133)
where
I
eNet
= Uncompensated earth-fault current of the network taking into account the
decentralized compensation.
3I> = Setting of the low-set overcurrent stage of the protected feeder
The magnitude of the minimum expected cross-country fault current can be
coarsely estimated based on the knowledge of the maximum earthing resistance
values,
Maximum earthing Ris, of all the feeders in the substation, and using the
following equation:
(Equation 134)
where
I
F_XCmin
= Minimum expected cross-country fault current
U
n_PE
= Nominal phase-to-earth voltage
Y
F1
= 1 /
Maximum earthing Ris = Admittance corresponding to the set maximum
earthing resistance value of the protected feeder
Y
F2
= 1 / max(
Maximum earthing Ris_i) = Admittance corresponding to the
maximum of the set earthing resistance values of other feeders in the substation
X
k
= Sum of short-circuit reactances of the incoming HV-network and main
transformer referred to MV-side
R
k
= Sum of short-circuit resistances of the incoming HV-network and main
transformer referred to MV-side
Example 1:
•
U
n_PE
= 11.547 kV
•
Maximum earthing Ris = 15 ohm
•
Maximum earthing Ris_i = 10 ohm
•
X
k
= 2.2 ohm
•
R
k
= 0.2 ohm
•
3I> = 200 A
•
I
eNet
= 320 A
Using the above parameters
I
F_XCmin
equals 0.8 kA in order of magnitude, which
is also higher than the uncompensated earth-fault current of the network and the
setting of the low-set overcurrent stage of the protected feeder. So, setting
XC
stage A Str Val can be selected between I
eNet
= 320 A and
I
F_XCmin
= 800 A.
Assuming phase CT-ratio 400/1 A, the setting
XC stage A Str Val is selected to be
700 A (1.75*In).
Protection functions
1MRS759142 F
626
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......