ROVPTOV, START -output
TONGAPC: On delay time (ms)
TONGAPC, Q1 -output
MFADPSDE, OPERATE -output
MFADPSDE, START -output
MFADPSDE, BLOCK -input, inversed
Figure 332: Logic to release MFADPSDE at the time of resistor (re)connection
The logic enables exact operate time of MFADPSDE elapsed from time of resistor
(re)connection.
In the configuration, equal
Reset delay time and Voltage start value must
be used for ROVPTOV and MFADPSDE.
The release delay should be based on known delays in resistor (re)connection:
• Logic OFF-ON-OFF:
Switch on delay of the parallel resistor.
• Logic ON-OFF-ON:
Switch off delay + Time off time of the parallel resistor.
The resulting total protection operate time is defined as follows:
• Logic OFF-ON-OFF:
Switch on delay of the parallel re set Operate delay
time of MFADPSDE.
• Logic ON-OFF-ON:
Switch off delay + Time off time of the parallel re set
Operate delay time of MFADPSDE.
• Set
Operate delay time of MFADPSDE smaller than the connection duration time
of the resistor.
If earth faults are only alarmed, the external logic is not needed.
When the proposed logic is used and indication of transient earth faults is needed,
the
START
output from INTRPTEF can be used.
Timer
If the detected fault direction is opposite to the set directional mode and GFC
release is active,
BLK_EF
output is activated once
Start delay time has elapsed.
Reset timer is activated at the falling edge of GFC release, that is, when zero-
sequence voltage falls below
Voltage start value. BLK_EF is reset once the reset
delay time elapses. Activation of the
BLOCK
input deactivates the
BLK_EF
output
and resets Timer.
BLK_EF
output is activated when the following conditions are met:
• Earth fault is detected by the GFC
• Fault direction is opposite to
Directional mode setting
The estimated stabilized fundamental frequency residual current
I
o stab
1
exceeds
the internally fixed threshold, which is 1% of In. This current magnitude threshold
supervision is based on the “Amplitude” method.
1MRS759142 F
Protection functions
REX640
Technical Manual
577
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......