The protection relay is the CAM client and can maintain its own replica database
of the user accounts and roles configured in the CAM server. This CAM replica
database acts as a backup authentication mechanism if primary and secondary
CAM servers are not accessible from the protection relay.
Each protection relay supports eight roles and 50 user accounts in the CAM replica
database. Each user account can be mapped to a maximum of eight roles.
For more information on user management and security logging, see the
cyber security deployment guideline.
For user authorization for PCM600, see the PCM600 documentation.
2.8
Station communication
Operational information and controls are available through a wide range of
communication protocols including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC
60870-5-103, IEC 60870-5-104, Modbus
®
and DNP3. Full communication capabilities,
for example, horizontal communication between the relays, are only enabled by IEC
61850.
The relay provides the possibility for a second IP address and a second subnetwork
when the communication modules with three Ethernet ports (COM1001...1003) are
used. However, only one IP network can be used as the default route. Using two
IP addresses, communication networks can be separated based on the dominant
user’s needs. For example, one IP address can serve the dispatchers and the other
one can serve the service engineers’ needs.
The IEC 61850 protocol is a core part of the relay as the protection and control
application is fully based on standard modelling. The relay supports Edition 2 and
Edition 1 versions of the standard. With Edition 2 support, the relay has the latest
functionality modelling for substation applications and the best interoperability for
modern substations. The relay supports flexible product naming (FPN) facilitating
the mapping of relay’s IEC 61850 data model to a customer defined IEC 61850 data
model.
2.9
Modification Sales
Modification Sales is a concept that provides modification support for already
delivered relays. Under Modification Sales it is possible to modify both the hardware
and software capabilities of the existing relay. The same options are available as
when a new relay variant is configured and ordered from the factory: it is possible
to add new hardware modules into empty slots, change the type of the existing
modules within the slots or add software functions by adding application and, if
necessary, add-on packages. If it is needed to use the possibilities provided by the
Modification Sales concept, please contact your local ABB unit.
REX640 overview
1MRS759142 F
56
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......