identifying which relay requires operator’s attention when the bay overview is not
visible on the navigation page.
When the HMI view is opened for a relay, the SHMI works exactly like a normal HMI.
All the same features are available, and the Home button switches between the
configured home pages and indicates the alarm status for the respective relay.
Navigation area on the top left corner of the HMI view is used to navigate back to
the SHMI’s navigation page. The navigation area shows the bay name on the button
to identify which relay’s HMI is open.
2.5
Physical ports
The relay communication module has a dedicated port where the LHMI is connected
using an RJ-45 connector and a CAT 6 S/FTP galvanic cable. The HMI can be
connected to the relay also via station communication network if a longer distance
is required between the relay and the HMI. For more information, see the installation
manual.
Additionally, the HMI contains one Ethernet service port with an RJ-45 connector
and one USB port. The service port can be used for the PCM600 connection or
for WHMI connection. Data transfer to a USB stick is enabled via the USB port.
By default the USB port is disabled and has to be taken into use with a specific
parameter.
D
1
2
Figure 8: Local HMI connectors
1
USB port
2
RJ-45 ports
1MRS759142 F
REX640 overview
REX640
Technical Manual
53
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......