4.2.6.10
Technical data
Table 592: HAEFPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±5% of the set value or ±0.004 × I
n
Start time ,
Typically 77 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
3
±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode
±5.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = f
n
-3 dB at f = 13 × f
n
4.2.7
Wattmetric-based earth-fault protection WPWDE (ANSI
32N)
4.2.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Wattmetric-based earth-fault pro-
tection
WPWDE
Po> ->
32N
4.2.7.2
Function block
Figure 304: Function block
4.2.7.3
Functionality
The wattmetric-based earth-fault protection function WPWDE can be used to detect
earth faults in unearthed networks, compensated networks (Petersen coil-earthed
networks) or networks with a high-impedance earthing. It can be used as an
alternative solution to the traditional residual current-based earth-fault protection
functions, for example, the IoCos mode in the directional earth-fault protection
function DEFxPDEF.
1
Fundamental frequency current = 1.0 × I
n
, harmonics current before fault = 0.0 × I
n
, harmonics
fault current 2.0 ×
Start value, results based on statistical distribution of 1000 measurements.
2
Includes the delay of the signal output contact.
3
Start time of the function also included.
4
Maximum
Start value = 2.5 × I
n
,
Start value multiples in range of 2...20.
1MRS759142 F
Protection functions
REX640
Technical Manual
529
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......