Characteristic
Value
I
Fault
= 2 × set
Start
value
I
Fault
= 10 × set
Start
value
8 ms
8 ms
11 ms
9 ms
14 ms
11 ms
EFHPTOC and EFLP-
TOC
3
:
I
Fault
= 2 × set
Start
value
23 ms
26 ms
29 ms
Reset time
Typically <40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
5
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
4
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
4.2.1.13
Technical revision history
Table 527: EFLPTOC Technical revision history
Product
connectivi
ty level
Technical
revision
Change
PCL4
I
Setting
Start value
maximum value extended to 10.000xIn.
4.2.2
Directional earth-fault protection DEFxPDEF (ANSI
67G/N-1 51G/N-1, 67G/N-1 51G/N-2)
4.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional earth-fault protection,
low stage
DEFLPDEF
Io> ->
67G/N-1
Table continues on the next page
2
Measured with static signal output (SSO).
3
Includes the delay of the signal output contact (SO).
5
Start time of the function also included.
4
Maximum
Start value = 2.5 × I
n
,
Start value multiples in range of 1.5...20.
1MRS759142 F
Protection functions
REX640
Technical Manual
451
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......