Characteristic
Value
Retardation time
<35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
4.1.8
Loss of load supervision LOFLPTUC (ANSI 37)
4.1.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of load supervision
LOFLPTUC
3I<
37
4.1.8.2
Function block
Figure 233: Function block
4.1.8.3
Functionality
The loss of load supervision function LOFLPTUC is used to detect a sudden load
loss which is considered as a fault condition.
LOFLPTUC starts when the current is less than the set limit. It operates with the
definite time (DT) characteristics, which means that the function operates after a
predefined operate time and resets when the fault current disappears.
The function contains a blocking functionality. It is possible to block function
outputs, the definite timer or the function itself.
4.1.8.4
Analog channel configuration
LOFLPTUC has one analog group input which must be properly configured.
Table 459: Analog inputs
Input
Description
I3P
Three-phase currents
See the preprocessing function blocks in this document for the possible
signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
Protection functions
1MRS759142 F
402
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......