Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
Voltage: -50 dB at f = n × f
n
, where n = 2, 3, 4,
5, …
Current: No suppression
4.1.5
Three-phase thermal protection for feeders, cables and
distribution transformers T1PTTR (ANSI 49F)
4.1.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase thermal protection for
feeders, cables and distribution
transformers
T1PTTR
3Ith>F
49F
4.1.5.2
Function block
Figure 226: Function block
4.1.5.3
Functionality
The increased utilization of power systems closer to the thermal limits has
generated a need for a thermal overload function also for power lines.
A thermal overload is in some cases not detected by other protection functions,
and the introduction of the three-phase thermal protection for feeders, cables and
distribution transformers function T1PTTR allows the protected circuit to operate
closer to the thermal limits.
An alarm level gives an early warning to allow operators to take action before the
line trips. The early warning is based on the three-phase current measuring function
using a thermal model with first order thermal loss with the settable time constant.
If the temperature rise continues the function will operate based on the thermal
model of the line.
Re-energizing of the line after the thermal overload operation can be inhibited
during the time the cooling of the line is in progress. The cooling of the line is
estimated by the thermal model.
4.1.5.4
Analog channel configuration
T1PTTR has one analog group input which must be properly configured.
1MRS759142 F
Protection functions
REX640
Technical Manual
383
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......