Table 366: Proposed functionality of numerical transformer and busbar overcur-
rent protection. DT = definite time, IDMT = inverse definite minimum time
O/C-stage
Operating char.
Selectivity mode Operation speed
Sensitivity
HV/3I>
DT/IDMT
time selective
low
very high
HV/3I>>
DT
blockable/time
selective
high/low
high
HV/3I>>>
DT
current selective
very high
low
LV/3I>
DT/IDMT
time selective
low
very high
LV/3I>>
DT
time selective
low
high
LV/3I>>>
DT
blockable
high
high
In case the bus-tie breaker is open, the operating time of the blockable overcurrent
protection is approximately 100 ms (relaying time). When the bus-tie breaker is
closed, that is, the fault current flows to the faulted section of the busbar from two
directions, the operation time becomes as follows: first the bus-tie relay unit trips
the tie breaker in the above 100 ms, which reduces the fault current to a half. After
this the incoming feeder relay unit of the faulted bus section trips the breaker in
approximately 250 ms (relaying time), which becomes the total fault clearing time in
this case.
Figure 202: Numerical overcurrent protection functionality for a typical sub-
transmission/distribution substation (feeder protection not shown). Blocking
output = digital output signal from the start of a protection stage, Blocking in =
digital input signal to block the operation of a protection stage
The operating times of the time selective stages are very short, because the grading
margins between successive protection stages can be kept short. This is mainly due
to the advanced measuring principle allowing a certain degree of CT saturation,
good operating accuracy and short retardation times of the numerical units. So, for
1MRS759142 F
Protection functions
REX640
Technical Manual
335
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......