
3.22.4
Real subtraction SUBR
3.22.4.1
Function block
Figure 175: Function block
3.22.4.2
Functionality
The real subtraction function SUBR subtracts input
REAL_IN2
from
REAL_IN1
.
SUBR executes the equation
REAL_OUT
=
REAL_IN1
–
REAL_IN2
If the value of the difference is outside the range, then the output quality is
set as bad and
VALID
is set to FALSE. The minimum negative difference value is
restricted to –2097152.000 and the maximum positive difference value is restricted
to 2097152.000.
3.22.4.3
Signals
Table 321: SUBR Input signals
Name
Type
Default
Description
REAL_IN1
FLOAT32
0
Real input 1
REAL_IN2
FLOAT32
0
Real input 2
Table 322: SUBR Output signals
Name
Type
Description
REAL_OUT
FLOAT32
Real output
VALID
BOOLEAN
Output validity
3.22.5
Real equal comparator EQR
3.22.5.1
Function block
Figure 176: Function block
Basic functions
1MRS759142 F
302
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......