need to be blocked from the protection, the application configuration must be
used to block these signals. The blocking scheme needs to use
BEH_BLK
output of
PROTECTION function block.
BEH_BLK
signal can be used to
• Connect to TRPPTRC
BLOCK
input. This is the best option when all protection
signaling goes through the master trip function.
• Connect to necessary protection function
BLOCK
inputs.
• Create logic condition for physical outputs to block state changes when
BEH_BLK
is active.
11.8.3
Control mode
The mode of all logical nodes located under CTRL logical device can be set with
Control mode. The Control mode parameter is available via the HMI or PCM600
path Configuration > Control > General. By default,
Control mode can only be set
locally through LHMI.
Control mode inherits its value from Test mode but Control
mode ”On”, “Blocked” and “Off” can also be set independently. Control mode is also
available via IEC 61850 communication (CTRL.LLN0.Mod).
Table 1657: Control mode
Control mode
Description
Control BEH_BLK
On
Normal operation
FALSE
Blocked
Control function commands blocked
TRUE
Off
Control functions disabled
FALSE
See function block Control for more details.
The behavior data objects under CTRL logical device follow
CTRL.LLN0.Mod value. If "On" is selected, behavior data objects follow
the mode of the corresponding logical device.
11.8.4
Application configuration and Control mode
The physical outputs from commands to process are blocked with “Blocked“ mode.
If physical outputs need to be blocked totally, meaning also commands from the
binary inputs, the application configuration must be used to block these signals.
Blocking scheme uses
BEH_BLK
output of CONTROL function block.
11.8.5
Authorization
By default,
Test mode and Control mode can only be changed from LHMI. It is
possible to write test mode by remote client if it is needed in configuration. This
is done via LHMI by setting parameter
Test mode selection via Configuration >
System. Remote operation is possible only when the relay's control position is in
remote position. Local and remote control can be selected with R/L button or via
Control function block in application configuration.
1MRS759142 F
General function block features
REX640
Technical Manual
1913
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......