of the measurement window. The frequency of the fault current affects the operate
time. The damping of the harmonics is quite low and practically determined by the
characteristics of the anti-aliasing filter of the protection relay current inputs.
When using measurement mode “Wide P-to-P”, the protection relay
accepts only
Operate delay time setting value 800 ms or longer and
Operating curve type 5=”ANSI Def. Time” or 15=”IEC Def. Time”.
Operation accuracy in the frequency range 2...85 Hz is ±1.5% or ±0.003 × I
n
. Operate
time accuracy in definite time mode is ±1.0% of the set value or ±60 ms when I
Fault
=
2 × set
Start value and the fault current frequency is 10...85 Hz.
11.7
Calculated measurements
Calculated residual current and voltage
The residual current is calculated from the phase currents according to equation:
Io
I
I
I
A
B
C
= −
+
+
(
)
(Equation 404)
The residual voltage is calculated from the phase-to-earth voltages when the VT
connection is selected as “Wye” with the equation:
Uo
U
U
U
A
B
C
=
+
+
(
) / 3
(Equation 405)
Sequence components
The phase-sequence current components are calculated from the phase currents
according to:
I
I
I
I
A
B
C
0
3
=
+
+
(
) /
(Equation 406)
I
I
a I
a
I
A
B
C
1
2
3
=
+ ⋅
+
⋅
(
) /
(Equation 407)
I
I
a
I
a I
A
B
C
2
2
3
=
+
⋅
+ ⋅
(
) /
(Equation 408)
The phase-sequence voltage components are calculated from the phase-to-earth
voltages when
VT connection is selected as “Wye” with the equations:
U
U
U
U
A
B
C
0
3
=
+
+
(
) /
(Equation 409)
General function block features
1MRS759142 F
1910
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......