Table 1632: PHQVVR recording data bank parameters
Parameter description
Parameter name
Event detection triggering time stamp
Time
Variation type
Variation type
Variation magnitude Ph A
Variation Ph A
Variation magnitude Ph A time stamp (max-
imum/minimum magnitude measuring time
moment during variation)
Var Ph A rec time
Variation magnitude Ph B
Variation Ph B
Variation magnitude Ph B time stamp (max-
imum/minimum magnitude measuring time
moment during variation)
Var Ph B rec time
Variation magnitude Ph C
Variation Ph C
Variation magnitude Ph C time stamp (max-
imum/minimum magnitude measuring time
moment during variation)
Var Ph C rec time
Variation duration Ph A
Variation Dur Ph A
Variation Ph A start time stamp (phase A var-
iation start time moment)
Var Dur Ph A time
Variation duration Ph B
Variation Dur Ph B
Variation Ph B start time stamp (phase B var-
iation start time moment)
Var Dur Ph B time
Variation duration Ph C
Variation Dur Ph C
Variation Ph C start time stamp (phase C var-
iation start time moment)
Var Dur Ph C time
Current magnitude Ph A preceding variation
Var current Ph A
Current magnitude Ph B preceding variation
Var current Ph B
Current magnitude Ph C preceding variation
Var current Ph C
Table 1633: Enumeration values for the recorded data parameters
Setting name
Enum name
Value
Variation type
Swell
1
Variation type
Dip
2
Variation type
Swell + dip
3
Variation type
Interruption
4
Variation type
Swell + Int
5
Variation type
Dip + Int
6
Variation type
Swell+dip+Int
7
10.3.7
Application
Voltage variations are the most typical power quality variations on the public
electric network. Typically, short-duration voltage variations are defined to last
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1841
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......