Fast
transfer –
simulta-
neous
Enable/disable
Fast
transfer –
sequen�a
l
break
before
make
(FBBM)
Enable/disable
1st phase
transfer
Residual
voltage
transfer
Time
delayed
transfer
Enable/disable
Decoupling
Transfer
in
i�a�
on
Enable/disable
Enable/disable
Enable/disable
Figure 940: Transfer sequence steps
Fast transfer – simultaneous
A fast transfer takes place when both the main and the stand-by feeders are within
specified limit values at the moment of initiation, e.g. frequency slip and phase
angle difference are limited between the networks and the stand-by voltage lies
above a minimum value.
Fast transfer can be enabled with the setting
Enable fast transfer. If Enable fast
transfer setting is set to “1>2”, then fast transfer is allowed to the direction from
feeder 1 to feeder 2. If
Enable fast transfer setting is set to “2>1”, then fast transfer
is allowed to the direction from feeder 2 to feeder 1. Setting value “Both” allows
fast transfer to both directions. Fast transfer can be disabled by setting
Enable fast
transfer to “Off”.
If
Enable FBBM setting is set to “false”, then function executes simultaneous fast
transfer. In case
Enable FBBM is set to “true”, then function executes sequential
transfer.
In simultaneous fast transfer circuit breaker open and close commands are issued at
the same time (see
)
For uninterrupted transfer, the HSABTC function carries out a fast transfer, under
the condition that busbar and stand-by feeder are synchronous and other criteria as
described below are satisfied. For this the circuit breaker open and close signals are
issued simultaneously to the respective circuit breakers of main feeder and standby
feeder.
The fast transfer occurs in the direction of feeder 1 to feeder 2, if following
conditions are fulfilled simultaneously:
• The FAST_READY (from Evaluation module) is TRUE
• The READY (from Evaluation module) is TRUE
•
DISA_FAST
input is FALSE
•
DISA_1_2
input is FALSE
• Setting
Enable fast transfer is “1 > 2” or “Both”
• Transfer is activated as described in transfer initiation
The simultaneous fast transfer minimizes the dead time without current flow.
shows fast transfer with current free transfer time (dead time) of about
20ms. The dead time depends on the used circuit breakers and settings and this can
be optimized.
1MRS759142 F
Control functions
REX640
Technical Manual
1773
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......