9.11.4
Analog channel configuration
PASANCR has three analog group inputs which must be properly configured.
Table 1589: Analog inputs
Input
Description
U3P
Three-phase voltages
IRES
1
Residual current (measured or calculated)
URES
Residual voltage (measured)
See the preprocessing function blocks in this document for the possible
signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
9.11.5
Controller connections
Voltages
PASANCR supports zero-sequence voltage measurement from busbar or from
coil. Busbar measurement is, for example, an open-delta connection of phase-
to-earth voltage transformers. Coil measurement uses the coil's own secondary
measurement winding.
Voltage measurement setting is used to select the active
measurement. Available options are "Busbar" and "Coil".
Phase-to-phase voltage AB must be connected to the controller. If only the phase
voltages are measured, the voltage U_AB is calculated internally in the protection
relay.
Coil position
The controller supports two possibilities for the coil position measurement.
Position Meas mode setting is used to select the active coil position measurement.
Available options are:
• "Pos. indication": Using only the RTD input module to measure the resistance
value from the arc suppression coil potentiometer with
COIL_POS
input and to
convert it into corresponding coil position according to the linearization table.
• "Pos. ind. and meas.": Using both
COIL_POS
and
IRES
signals.
IRES
is arc
suppression coil current measurement using conventional CTs or sensors. Special
attention should be paid to the accuracy of the current signals at low amplitudes.
Additionally, high accuracy can be ensured by applying measurement class CTs
and sensors. Accurate current measurement improves controller speed and
1
The possible connection options are measured IRES from the coil/main transformer neutral
point, calculated IRES from the phase CTs of earthing transformer, or GRPOFF. If GRPOFF is
connected to IRES, the
Position Meas mode is restricted to "Pos. indication" only.
1MRS759142 F
Control functions
REX640
Technical Manual
1731
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......