9.10.10
Technical data
Table 1587: OL5ATCC Technical data
Characteristic
Value
Operation accuracy
1
Depending on the frequency of the measured
current: f
n
±2 Hz
Differential voltage U
d
= ±0.5% of the meas-
ured value or ±0.005 × U
n
(in measured vol-
tages <2.0 × U
n
)
Operation value = ±1.5 % of the U
d
for Us =
1.0 × U
n
Operate time accuracy in definite time mode
2
+4.0 %/-0 % of the set value
Operate time accuracy in inverse time mode
2
+8.5 %/-0 % of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time
(IDMT) 1 s.
Reset ratio for control operation
Reset ratio for analog based blockings (ex-
cept run back raise voltage blocking)
Typically 0.80 (1.20)
Typically 0.96 (1.04)
9.10.11
Technical revision history
Table 1588: OL5ATCC Technical revision history
Product connectivity
level
Technical revision
Change
PCL2
B
Added new output
TAP_DIFF
for indicating
the difference in tap position between mas-
ter and follower
Changed the
Band width voltage
minimum
value to "1.00"
Added setting
Inst out of step Cor
for en-
abling triggering of instant out-of-step se-
quence in M/F mode
PCL4
C
Added new inputs I3P2, U3P2, PWR_DIR. Add-
ed new output REV_REG. Added new set-
tings
Regulation mode
,
Step of Tap
,
Tap nom-
inal
and
Impedance voltage
. Updated the im-
plementation to handle HV side regulation
during reverse power flow from stronger
sources.
1
Default setting values used.
2
Voltage before deviation = set
Band center voltage.
1MRS759142 F
Control functions
REX640
Technical Manual
1729
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......