SOTF is activated when the AR function is enabled or when the AR function is
started and the SOTF should remain active for the reclaim time.
When SOTF is detected, the parameter
SOTF is active.
If the
Manual close mode setting is set to FALSE and the circuit breaker
has been manually closed during an autoreclosing shot, the AR unit goes
to an immediate lockout.
If the
Manual close mode setting is set to TRUE and the circuit breaker
has been manually closed during an autoreclosing shot (the INPRO is
active), the shot is considered as completed.
When SOTF starts, reclaim time is restarted, provided that it is running.
The frequent-operation counter is intended for blocking the autoreclosing function
in cases where the fault causes repetitive autoreclosing sequences during a short
period of time. For instance, if a tree causes a short circuit and, as a result, there
are autoreclosing shots within a few minutes interval during a stormy night. These
types of faults can easily damage the circuit breaker if the AR function is not locked
by a frequent-operation counter.
The frequent-operation counter has three settings:
•
Frq Op counter limit
•
Frq Op counter time
•
Frq Op recovery time
The
Frq Op counter limit setting defines the number of reclose attempts that are
allowed during the time defined with the
Frq Op counter time setting. If the set
value is reached within a pre-defined period defined with the
Frq Op counter time
setting, the AR function goes to lockout when a new shot begins, provided that
the counter is still above the set limit. The lockout is released after the recovery
time has elapsed. The recovery time can be defined with the
Frq Op recovery time
setting .
If the circuit breaker is manually closed during the recovery time, the reclaim time is
activated after the recovery timer has elapsed.
9.9.5
Counters
The AR function contains six counters. Their values are stored in a semi-retain
memory. The counters are increased at the rising edge of the reclosing command.
The counters count the following situations.
• COUNTER: counts every reclosing command activation
• CNT_SHOT1: counts reclosing commands that are executed from shot 1
• CNT_SHOT2: counts reclosing commands that are executed from shot 2
• CNT_SHOT3: counts reclosing commands that are executed from shot 3
• CNT_SHOT4: counts reclosing commands that are executed from shot 4
• CNT_SHOT5: counts reclosing commands that are executed from shot 5
The counters are disabled through communication with the
DsaCnt parameter.
When the counters are disabled, the values are not updated.
1MRS759142 F
Control functions
REX640
Technical Manual
1677
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......