
active longer than necessary, the
CMD_FAIL_AL
alarm output is activated. To avoid
unnecessary alarms, the maximum length of the closing command signal should be
below
Maximum Syn time + 5 s.
CLOSE_CB
t =
Maximum Syn time
CMD_FAIL_AL
t = 5 s
CL_COMMAND or
Synchronize CB
Figure 878: Determination of the alarm limit for a still-active command signal
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates all binary outputs and resets the internal timers.
9.7.6
Application
A circuit breaker is used to connect two different power networks. It is essential
to ensure that these power networks are synchronized before closing the CB,
otherwise it may lead to disturbances in the power system, causing stress and
damage to the connected equipment.
ASNSCSYN can be used for the synchronized closing of a non-generator circuit
breaker such as a bus sectionalizer, a bus coupler or an incoming feeder. It
checks for the synchronization conditions across the CB and releases the CB
closing command. If these conditions are not fulfilled, the sources in the power
network connected across this bus coupler or tie feeder CB have to change their
operating points to meet the requirements. This is achieved with Autosynchronizer
co-ordinator ASCGAPC available with the source (ASGCSYN) function and non-
source (ASNSCSYN) function.
ASCGAPC assists in the participating sources selection based on the network
topology and interacts with the sources to initiate the voltage and frequency
matching for the bus coupler or tie feeder CB to be synchronized. When any non-
source circuit breaker (NSCB) is selected for synchronization, a synchronization
procedure is started. ASCGAPC located in the NSCB relay starts communicating
with ASCGAPCs of possible source circuit breaker (SCB) relays for matching the
voltage and frequency difference. Both ASCGAPCs pass the required information to
the participating sources. A non-source CB synchronization is described with one
typical example in
1MRS759142 F
Control functions
REX640
Technical Manual
1599
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......