calculated voltage and frequency difference across the circuit breaker to be
synchronized. ASGCSYN also participates in voltage and frequency matching for
network breaker synchronization.
9.6.4
Analog channel configuration
ASGCSYN has two analog group inputs which must be properly configured.
Table 1513: Analog inputs
Input
Description
U3P1
Three-phase voltages (generator side)
U3P2
Three-phase voltages (bus side)
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 1514: Special conditions
Condition
Description
U3P1 and U3P2 connected to
real measurements
When one voltage channel from the generator side is connec-
ted to channel 1 of
U3P1
and one voltage channel from the
bus side is connected to channel 1 of
U3P2
, the function can
only work if UTVTR's
VT connection
settings on the genera-
tor and bus sides are similar.
The function can work if one voltage channel from the gen-
erator side is connected to channel 1 of
U3P1
and three
voltage channels from the bus side are connected to
U3P2
.
The function can work if one voltage channel from the gener-
ator side is connected to channel 1 of
U3P1
and two voltage
channels along with the residual voltage from the bus side
are connected to
U3P2
.
The function can work if three voltage channels from the
generator side are connected to
U3P1
and one voltage chan-
nel from the bus side is connected to channel 1 of
U3P2
.
The function can work if two voltage channels and the resid-
ual voltage from the generator side are connected to
U3P1
and one voltage channel from the bus side is connected to
channel 1 of
U3P2
.
Dissimilar VT connection set-
tings for UTVTR on the gener-
ator and bus sides
The function requires that all three voltage channels or two
voltage channels and the residual voltage are connected to
either
U3P1
or
U3P2
.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
Control functions
1MRS759142 F
1558
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......