9.6
Autosynchronizer for generator breaker ASGCSYN
(ANSI 25AUTOSYNCG)
9.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autosynchronizer for generator
breaker
ASGCSYN
AUTOSYNCG
25AUTOSYNCG
9.6.2
Function block
Figure 853: Function block
9.6.3
Functionality
The autosynchronizer for generator breaker function ASGCSYN checks the
conditions across the circuit breaker from generator and bus side and issues
the pulse commands to the automatic voltage regulator (AVR) and prime mover
governor to match the voltage and frequency conditions if required. Once the
synchronization check and close CB conditions are fulfilled, the function gives
permission to close the circuit breaker. ASGCSYN includes the functionality of
energizing check, synchronization check and voltage and frequency matching.
The energizing check function checks that bus side is dead to ensure that
breaker closing can be done safely. The synchronization check function checks that
the voltages and frequency on both sides of the circuit breaker are within the
predefined setting. It is used to perform a controlled reconnection of two systems.
Depending on the selected control mode, the synchronization process is fully
automatic or it requires operator action for breaker closing and voltage and
frequency matching. In all of the modes, the synchronization check prevents breaker
closing if the set limit values are not met.
The voltage and frequency matching function issues raise or lower pulse commands
to AVR and the governor to match the voltage and frequency, based on the
1MRS759142 F
Control functions
REX640
Technical Manual
1557
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......