lags by 330 degrees the high-voltage-side phasor. The rotation of the phasors is
counterclockwise.
The generic rule is that a low-voltage-side phasor lags the high-voltage-side phasor
by clock number * 30º. This is called angle difference adjustment and can be set for
SECRSYN with the
Phase shift setting.
9.5.6
Application
The main purpose of the synchrocheck function is to provide control over the
closing of the circuit breakers in power networks to prevent the closing if the
conditions for synchronism are not detected. This function is also used to prevent
the reconnection of two systems which are divided after islanding and a three-pole
reclosing.
The Synchro check function block includes both the synchronism check function and
the energizing function to allow closing when one side of the breaker is dead.
Network and the generator running in parallel with the network are connected
through the line AB. When a fault occurs between A and B, the protection relay
protection opens the circuit breakers A and B, thus isolating the faulty section
from the network and making the arc that caused the fault extinguish. The first
attempt to recover is a delayed autoreclosure made a few seconds later. Then, the
autoreclose function DARREC gives a command signal to the synchrocheck function
to close the circuit breaker A. SECRSYN performs an energizing check, as the line AB
is de-energized (
U_BUS
>
Live bus value,
U_LINE
<
Dead line value) . After verifying
the line AB is dead and the energizing direction is correct, the protection relay
energizes the line (
U_BUS
->
U_LINE
) by closing the circuit breaker A. The PLC of
the power plant discovers that the line has been energized and sends a signal to
the other synchrocheck function to close the circuit breaker B. Since both sides of
the circuit breaker B are live (
U_BUS
>
Live bus value,
U_LINE
>
Live bus value),
the synchrocheck function controlling the circuit breaker B performs a synchrocheck
and, if the network and the generator are in synchronism, closes the circuit breaker.
G
SECRSYN
DARREC
SECRSYN
PLC
A
B
U_Bus
U_Bus
U_Line
U_Line
Figure 851: Synchrocheck function SECRSYN checking energizing conditions and
synchronism
Control functions
1MRS759142 F
1552
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......