9.5.3
Functionality
The synchronism and energizing check function SECRSYN checks the condition
across the circuit breaker from separate power system parts and gives the
permission to close the circuit breaker. SECRSYN includes the functionality of
synchrocheck and energizing check.
Asynchronous operation mode is provided for asynchronously running systems.
The main purpose of the asynchronous operation mode is to provide a controlled
closing of circuit breakers when two asynchronous systems are connected.
The synchrocheck operation mode checks that the voltages on both sides of
the circuit breaker are perfectly synchronized. It is used to perform a controlled
reconnection of two systems which are divided after islanding and it is also used to
perform a controlled reconnection of the system after reclosing.
The energizing check function checks that at least one side is dead to ensure that
closing can be done safely.
The function contains a blocking functionality. It is possible to block function
outputs and timers.
9.5.4
Analog channel configuration
SECRSYN has two analog group inputs which must be properly configured.
Table 1502: Analog inputs
Input
Description
U3P1
Three-phase voltages (bus side)
U3P2
Three-phase voltages (line side)
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 1503: Special conditions
Condition
Description
U3P1 connected to real meas-
urements
The function requires that at least two voltage channels from
the bus side are connected.
U3P2 connected to real meas-
urements
The function requires that one voltage channel from the line
side is connected to channel 1 or any two voltage channels
from the line side.
When a single voltage channel is connected on the line side, the
VT connection
setting of the U3P2 source UTVTR defines whether ph-to-earth or ph-to-ph voltages
are used from both sides in checking the conditions. If at least two voltage channels
are connected on line side, ph-to-ph voltages are used from both sides in checking
the conditions regardless of the
VT connection settings of the source UTVTRs.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
Control functions
1MRS759142 F
1544
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......