
The recording always contains all binary channels of the disturbance recorder. If one
of the binary channels is disabled, the recorded state of the channel is continuously
FALSE and the state changes of the corresponding channel are not recorded.
The corresponding channel name for disabled binary channels in the COMTRADE
configuration file is Unused BI.
To enable or disable an analog or a binary channel of the disturbance recorder, the
Operation parameter of the corresponding analog or binary channel is set to "on" or
"off".
The states of manual triggering and periodic triggering are not included in the
recording, but they create a state change to the
Periodic triggering and Manual
triggering status parameters, which in turn create events.
The
TRIGGERED
output can be used to control the indication LEDs of the protection
relay. The triggering of the disturbance recorder sets the
TRIGGERED
output to
TRUE. The output remains in this state until all the data for the corresponding
recording has been recorded.
The IP number of the protection relay and the value of the
Bay name
parameter are both included in the COMTRADE configuration file for
identification purposes.
8.2.5
Application
The disturbance recorder is used for post-fault analysis and for verifying the correct
operation of protection relays and circuit breakers. It can record both analog and
binary signal information. The analog inputs are recorded as instantaneous values
and converted to primary peak value units when the protection relay converts the
recordings to the COMTRADE format.
COMTRADE is the general standard format used for storing disturbance
recordings.
The binary channels are sampled once per task execution of the disturbance
recorder. The task execution interval for the disturbance recorder is the same as
for the protection functions. During the COMTRADE conversion, the digital status
values are repeated so that the sampling frequencies of the analog and binary
channels correspond to each other. This is required by the COMTRADE standard.
The disturbance recorder follows the 1999 version of the COMTRADE
standard and uses the binary data file format.
8.2.6
Signals
Table 1438: RDRE Output signals
Name
Type
Description
TRIGGERED
BOOLEAN
Recording started
8.2.7
Settings
1MRS759142 F
Measurement functions
REX640
Technical Manual
1493
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......