8.2.3.10
Exclusion mode
Exclusion mode is on when the value of the
Exclusion time parameter is higher
than zero. During the exclusion mode, new triggerings are ignored if the triggering
reason is the same as in the previous recording. The
Exclusion time parameter
controls how long the exclusion of triggerings of same type is active after a
triggering. The exclusion mode applies only to the analog and binary channel
triggerings, not to periodic and manual triggerings.
When the value set with the
Exclusion time parameter is zero, the exclusion mode
is disabled and there are no restrictions on the triggering types of the successive
recordings.
The exclusion time setting is global for all inputs, but there is an individual counter
for each analog and binary channel of the disturbance recorder, counting the
remaining exclusion time. The remaining exclusion time can be monitored with
the
Exclusion time rem parameter (only visible via communication, IEC 61850 data
ExclTmRmn) of the corresponding analog or binary channel. The
Exclusion time rem
parameter counts downwards.
8.2.4
Configuration
The disturbance recorder can be configured with PCM600 or any tool supporting
the IEC 61850 standard.
RDRE1 should always be included in Application Configuration when the
disturbance recorder is used.
The disturbance recorder can be enabled or disabled with the
Operation parameter
under the Configuration > Disturbance recorder > General menu.
One analog signal type of the protection relay can be mapped to each of the
analog channels of the disturbance recorder. The mapping is done in Application
Configuration in PCM600. The name of the analog channel is user-configurable.
It can be modified by defining a new name to the
Channel id text parameter of
the corresponding analog channel.
Channel id text can be edited in Application
Configuration by selecting the input channel and defining a new
Instance Name for
the channel in the Object Properties window.
Any external or internal digital signal of the protection relay which can be
dynamically mapped can be connected to the binary channels of the disturbance
recorder. These signals can be, for example, the start and trip signals from
protection function blocks or the external binary inputs of the protection relay. The
connection is made with dynamic mapping to the binary channel of the disturbance
recorder using, for example, Signal Matrix of PCM600. It is also possible to connect
several digital signals to one binary channel of the disturbance recorder. In that
case, the signals can be combined with logical functions, for example AND and OR.
The name of the binary channel can be modified by defining a new name to the
Channel id text parameter of the corresponding channel. Channel id text can be
edited in Application Configuration by selecting the input channel and defining a
new
Instance Name for the channel in the Object Properties window.
The
Channel id text parameter is used in COMTRADE configuration files
as a channel identifier.
Measurement functions
1MRS759142 F
1492
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......