
faults)/ reactive power (for excitation faults) falls below 2% of nominal value, the
OPERATE
output is activated to open the generator circuit breaker.
In case the active or reactive power does not fall below 2% of nominal value within
the set
Operate delay time, after the activation of
STOP_ENGINE
or
DE_EXCITE
outputs respectively, the
EXTERNAL_FLT
output is activated along with
OPERATE
output.
The
Min active power, Max active power, Min reactive power and Max
reactive power settings should be set such that the faulty generator
is tripped by its own DGMGAPC function before a healthy generator is
tripped on over/under power/excitation condition.
The opening of the generator circuit breaker is monitored through the inputs
GCB_CLOSED
and
GCB_OPEN
. If the confirmation of GCB opening is not obtained
with in the set
Max CB trip delay, from the instant of activating
OPERATE
output,
the
OPR_TIE_A
and
OPR_TIE_B
outputs are activated to trip the tie breakers and
GCB_TRP_FAIL
output is activated.
If any of the inputs
GEN1_DATA … GEN8_DATA
indicate that backup protection is
triggered in one of the generators in its own subnetwork, then the module activates
the outputs
OPR_TIE_A
and
OPR_TIE_B
after the set
Backup delay time, to protect
the local diesel generator from tripping due to faults in other network generators.
The module continues to monitor the tie breaker status through inputs
TIE_A_CLOSED, TIE_A_OPEN, TIE_B_CLOSED
and
TIE_B_OPEN
. If after another
Max CB trip delay, the confirmed opening information of tie breakers is not
obtained then the module activates
TIE_TRP_FAIL
output.
The information on tie A or tie B side breaker tripping failure is shared with other
DGMGAPC functions in the network through output
GEN_DATA
to initiate tripping
of tie breaker. If the DGMGAPC function receives tie breaker trip failure indication
from a generator which shares a tie breaker with the local generator, then the
module initiates tripping of that shared tie breaker through either or both outputs
OPR_TIE_A
and
OPR_TIE_B
to protect the local generator.
The activated binary outputs,
OPERATE, OPR_TIE_A, OPR_TIE_B
and
EXTERNAL_FLT
, will remain active unless the
RESET
input is activated either from
LHMI or through communication.
The module combines the binary information, namely, the GCB status, adjacent tie
breaker statuses, Governor Mode, AVR mode, Generator local mode information,
backup protection activation (
BCKUP_PRT_ST
), fault status of the generator
(
PRE_TRIP
activation), A or B side tie breaker trip failure indication into output
GEN_DATA
. This output is available in the monitored data and is communicated
to other DGMGAPC functions in the network on GOOSE. The active and reactive
power inputs of the local generator are also communicated over GOOSE for usage
as inputs in other DGMGAPC functions.
The binary input
BLOCK
can be used to block the function, for example, during
synchronization of switchboard sections and when the engine is placed in manual
control. The activation of the
BLOCK
input deactivates all module binary outputs,
binary monitored data and resets the internal timers.
7.5.6
Application
The function is intended towards a set of diesel generators with similar
characteristics interconnected with busbar and tie-breakers.
Condition monitoring functions
1MRS759142 F
1418
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......