Figure 791: Location of top oil sensor
WARNING
and
ALARM
signals are provided for the operator to take corrective
actions to reduce the temperature inside the transformer. Corrective actions include
switching on coolers, reducing the load on the transformers and so on.
Normally, warning level is set to indicate if the temperature is nearing
the limiting value and alarm is generated when the limiting condition has
reached. Hence, alarm level is set at a higher value than the warning level.
The function only calculates hot-spot temperature based on the load factor of the
winding. This function does not calculate the rise in actual hot-spot temperature,
which occurs due to oil flow blockage or malfunction of cooler groups. That said,
the set oil and winding properties can be updated manually to indicate this change.
Based on the calculated hot-spot temperature, the function calculates the relative
ageing, that is, the accelerated or decelerated ageing of the insulation at current
load compared to its ageing at rated load. The variation of ageing acceleration
factor with respect to the hot-spot temperature for a sample transformer is plotted
. Here, 110 °C is taken as the rated hot-spot temperature at which point
an ageing acceleration factor of 1.0 is achieved.
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1393
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......