3.8.6
Station authority level "L,S,R"
Station authority level "L,S,R" adds station control access. In this level IEC 61850
command originator category validation is performed to distinguish control
commands with IEC 61850 command originator category set to “Remote” or
“Station”. There is no multilevel access.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
OFF
LOCAL
REMOTE
STATION
Figure 53: Station authority is “"L,S,R"
When the station authority level “L,S,R” is used, the control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are applicable for
this station authority level.
Station control access can be reserved by using R/L button or CONTROL function
block together with IEC 61850 data object CTRL.LLN0.LocSta
Table 75: Station authority level “L,S,R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
Local
FALSE
FALSE
1
x
Remote
FALSE
FALSE
2
x
Remote
TRUE
FALSE
3
x
Off
FALSE
FALSE
0
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
1MRS759142 F
Basic functions
REX640
Technical Manual
139
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......