3.8.5
Station authority level "L,R,L+R"
Station authority level "L,R, L+R" adds multilevel access support. Control access can
also be simultaneously permitted from local or remote location. Simultaneous local
or remote control operation is not allowed as one client and location at time can
access controllable objects and they remain reserved until the previously started
control operation is first completed by the client. Control access with IEC61850
originator category station is interpreted as remote access.
IEC 61850
remote
IED
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
L+R
IEC 61850
remote
IEC 61850
remote
IED
REMOTE
LOCAL
OFF
Figure 52: Station authority is “L,R,L+R”
When station authority level "L,R, L+R" is used, the control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are not applicable
for this station authority level.
Table 73: Station authority level "L,R,L+R" using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocSta CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKey
HMI
Local user
IEC 61850 client
1
Local
N/A
FALSE
1
x
Remote
N/A
FALSE
2
x
Local + Remote
N/A
TRUE
4
x
x
Off
N/A
FALSE
0
Table 74: Station authority “L,R,L+R” using CONTROL function block
L/R Control
L/R Control status
Control access
Control FB input
CTRL.LLN0.LocSta CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKey
HMI
Local user
IEC 61850 client
2
CTRL_OFF
N/A
FALSE
0
CTRL_LOC
N/A
FALSE
1
x
CTRL_STA
N/A
FALSE
0
CTRL_REM
N/A
FALSE
2
x
CTRL_ALL
N/A
TRUE
4
x
x
1
Client IEC 61850 command originator category check is not performed.
2
Client IEC 61850 command originator category check is not performed.
Basic functions
1MRS759142 F
138
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......