the change is detected on the healthy sets of CT, it is an indication of system
failure.
• A zero current due to the CT failure does not result in a phase angle difference
between the healthy phases.
If a system faults happens on the phase A, it results in a change in the phase
angle difference between phase B and phase C. This change in the phase angle
difference between the healthy phases is evaluated in all three sets of current
transformer, and if the change is detected in any set of CT, it is an indication of
the system failure.
If both conditions are satisfied at zero current, the
FAIL
output is activated
immediately. The
ALARM
output is activated after a fixed 200 ms delay.
FAIL
needs to be active during the delay. The outputs
FAIL
,
CTGRP1
,
FAIL_CTGRP2
and
FAIL_CTGRP3
are activated according to the CT group where the secondary failure
is detected.
Activation of the
BLOCK
input deactivates the
FAIL
and
ALARM
outputs.
It is not possible to detect the CT secondary failure happening
simultaneously with the system faults or failures or two simultaneous
failures in the secondary circuit. The function resets if the zero current
does not exist longer than 200 ms.
Internal blocking
This module blocks the function internally under specific condition to avoid any
false operation during a system fault situation. When any of the following condition
is satisfied, the function is internally blocked and the
FAIL
output is deactivated
immediately.
• Magnitude of any phase current for any group of current transformers exceeds
the
Max operate current setting. The magnitude of phase current is calculated
from the peak-to-peak value.
• Magnitude of the negative-sequence current I
2
on the healthy set of current
transformer exceeds the
Max Nq Seq current setting.
The
INT_BLKD
output is activated when
FAIL
is deactivated if any of the above
conditions is satisfied. The
ALARM
output is also deactivated after a fixed three-
second delay after the
FAIL
output is deactivated.
6.9.6
Application
Open or short-circuited current transformer secondary can cause unwanted
operation in many protection functions, such as earth-fault current and differential.
The simplest method for detecting the current transformer secondary failure is by
comparing currents from two independent three-phase sets of CTs or the CT cores
measuring the same primary currents. Another widely used method is the detection
of a zero-sequence current and zero-sequence voltage. The detection of a zero-
sequence current in the absence of a zero-sequence voltage is an indication of the
current transformer secondary failure. However, both methods have disadvantages
as they require an additional set of current transformer, or a voltage channel is
needed for detecting a zero-sequence voltage.
The methods may not be applicable where additional current channels or voltage
channels are not available. This CT secondary circuit supervision presents an
algorithm that can be used as an example for detecting the CT secondary failure
1MRS759142 F
Supervision functions
REX640
Technical Manual
1355
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......