6.8.10
Technical data
Table 1302: MSVPR Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
20 Hz < f ≤ 70 Hz: ±1.5 % of the set value or
±0.002 × U
n
10 Hz < f ≤ 20 Hz: ±4.0 % of the set value or
±0.002 × U
n
Reset time
Typically 40 ms
Reset ratio
Typically 1.04
Operate time accuracy in definite time mode ±1.0 % of the set value or ±20 ms
6.9
Current circuit supervision for transformers
CTSRCTF (ANSI CCM 3I,I2)
6.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision for trans-
formers
CTSRCTF
MCS 3I,I2
CCM 3I,I2
6.9.2
Function block
Figure 768: Function block
6.9.3
Functionality
The current circuit supervision for transformers function CTSRCTF is used for
monitoring the current transformer secondary circuit where a separate reference
current transformer input for comparison is not available or where a separate
voltage channel for calculating or measuring the zero-sequence voltage is not
available. CTSRCTF can be used for detecting the single-phase failure on the current
transformer secondary for protection application involving two or three sets of the
three-phase current transformers.
Supervision functions
1MRS759142 F
1352
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......