3.7.2.4
Special function block outputs
The function block has a few outputs dedicated for special purposes.
Table 66: Special function block outputs
Output
Description
CNF_CHANGE
Any setting change in the protection relay activates this out-
put for a short period of time (100...200 ms).
GRPOFF
Some application function blocks do now allow unconnected
analog inputs. In such a case,
GRPOFF
must be connected to
such an input.
DEV_WARN
A protection relay's internal warning activates this output.
For more information, see Warnings under the Self-supervi-
sion section.
3.7.3
Signals
Table 67: PROTECTION Input signals
Name
Type
Default
Description
BI_SG2
BOOLEAN
0
Setting group 2 is ac-
tive
BI_SG3
BOOLEAN
0
Setting group 3 is ac-
tive
BI_SG4
BOOLEAN
0
Setting group 4 is ac-
tive
BI_SG5
BOOLEAN
0
Setting group 5 is ac-
tive
BI_SG6
BOOLEAN
0
Setting group 6 is ac-
tive
MOD_TEST
BOOLEAN
0
Activation of test
mode
MOD_BLK
BOOLEAN
0
Block test mode
Table 68: PROTECTION Output signals
Name
Type
Description
SG_LOGIC_SEL
BOOLEAN
Logic selection for setting group
SG_1_ACT
BOOLEAN
Setting group 1 is active
SG_2_ACT
BOOLEAN
Setting group 2 is active
SG_3_ACT
BOOLEAN
Setting group 3 is active
SG_4_ACT
BOOLEAN
Setting group 4 is active
SG_5_ACT
BOOLEAN
Setting group 5 is active
SG_6_ACT
BOOLEAN
Setting group 6 is active
CNF_CHANGE
BOOLEAN
Active after any setting change
BEH_TEST
BOOLEAN
Logical device LD0 test status
BEH_BLK
BOOLEAN
Logical device LD0 block status
Table continues on the next page
Basic functions
1MRS759142 F
134
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......