Fuse failure detection criterion
Conditions and function response
The
FUSEF_U
output signal is also activated
if all the phase voltages are above the
Seal
in voltage
setting for more than 60 seconds
and at the same time the negative sequence
voltage is above
Neg Seq voltage Lev
for
more than 5 seconds, all the phase currents
are below the
Current dead Lin Val
setting
and the circuit breaker is closed, that is,
CB_CLOSED
is TRUE.
Current and voltage delta function criterion
If the current and voltage delta criterion de-
tects a fuse failure condition, but all the vol-
tages are not below the
Seal in voltage
set-
ting, only the
FUSEF_U
output is activated.
If the fuse failure detection is active for more
than five seconds and at the same time all
the phase voltage values are below the set
value of the
Seal in voltage
setting with
Ena-
ble seal in
turned to "True", the function acti-
vates the
FUSE_3PH
output signal.
External fuse failure detection
The
MINCB_OPEN
input signal is supposed
to be connected through a protection relay
binary input to the N.C. auxiliary contact of
the miniature circuit breaker protecting the
VT secondary circuit. The
MINCB_OPEN
sig-
nal sets the
FUSEF_U
output signal to block
all the voltage-related functions when MCB is
in the open state.
The
DISCON_OPEN
input signal is supposed
to be connected through a protection relay
binary input to the N.C. auxiliary contact of
the line disconnector. The
DISCON_OPEN
signal sets the
FUSEF_U
output signal to
block the voltage-related functions when the
line disconnector is in the open state.
It is recommended to always set
Enable seal in to "True". This secures
that the blocked protection functions remain blocked until normal
voltage conditions are restored if the fuse failure has been active for
5 seconds, that is, the fuse failure outputs are deactivated when the
normal voltage conditions are restored.
The activation of the
BLOCK
input deactivates both
FUSEF_U
and
FUSEF_3PH
outputs.
6.5.6
Application
Some protection functions operate on the basis of the measured voltage value
in the protection relay point. These functions can fail if there is a fault in the
measuring circuits between the voltage transformer (or combi sensor or voltage
sensor) and protection relay.
1MRS759142 F
Supervision functions
REX640
Technical Manual
1335
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......