6.3
Current transformer supervision for high-
impedance protection scheme HZCCxSPVC (ANSI
CCM_A, CCM_B, CCM_C)
6.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current transformer supervision for
high-impedance protection scheme
for phase A
HZCCASPVC
MCS I_A
CCM_A
Current transformer supervision for
high-impedance protection scheme
for phase B
HZCCBSPVC
MCS I_B
CCM_B
Current transformer supervision for
high-impedance protection scheme
for phase C
HZCCCSPVC
MCS I_C
CCM_C
6.3.2
Function block
Figure 751: Function block
6.3.3
Functionality
The current transformer supervision for high-impedance protection scheme
function HZCCxSPVC is a dedicated phase-segregated supervision function to be
used along with the high-impedance differential protection for detecting the broken
CT secondary wires. The differential current is taken as an input for the protection
relay. During normal CT condition, the value of the differential current is zero.
However, when the CT is broken, the secondary differential current starts flowing
and it is used for generating alarms.
To avoid maloperation, HZCCxSPVC should have a sensitive setting, compared to
the high-impedance differential protection. The function is likely to start under
through-fault conditions. However, by incorporating a high time delay (3 s or more),
the downstream protection clears the fault before an alarm is generated.
HZCCxSPVC generates an alarm when the differential current exceeds the set limit.
The function operates within the DT characteristic.
HZCCxSPVC contains a blocking functionality. It is possible to block the function
output, Timer or the whole function.
1MRS759142 F
Supervision functions
REX640
Technical Manual
1319
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......